Table 7

Comparison of ISO 10052 based survey method and proposed survey method bases on the KS and Korean building regulations.

ISO 10052 Proposed
Source room
  • Near the centre of the source room.

  • A single position is sufficient if the floor and slab are isotropic.

  • Centre point of the room

  • Centre and one perimeter point at the window side

  • Perimeter point: 0.75 m from the boundary walls or windows

Receiving room
  • Two fixed positions including that near the centre position, at different heights.

  • Distances between the microphones and room boundaries is 0.5 m.

  • Centre point of the room.

  • Centre and one perimeter point at the window side.

  • Height: 1.2 m.

  • Perimeter point: 0.75 m from the boundary walls or windows.

SNQ
  • A-weighted maximum impact sound pressure level (LiA,Fmax) with octave bands (63–500 Hz).

  • Overall A-weighted maximum impact sound pressure level (measured directly using the sound level meter).

  • A-weighted maximum impact sound pressure level (LiA,Fmax) with octave bands (63–500 Hz).