Sound power levels of compressor noise LW,comp using the example of the demonstrator heat pump at standard rating condition A7W55. The overall sound power level is calculated from 50 Hz to 16 kHz.

nc LW LWA LWLWA TAir Tc
rpm dB dB(A) dB °C °C
5500 57.8 52.4 5.4 6.5 55.2
5400 56.3 51.4 4.9 7.5 55.6
5100 55.1 50.3 4.8 7.4 55.4
5000 54.7 50.2 4.5 7.4 55.2
4800 53.6 49.7 3.9 7.0 54.7
4500 55.0 51.2 3.8 6.5 55.2
4200 54.3 48.4 5.9 6.8 55.0
4000 57.3 48.8 8.5 6.6 54.9
3900 55.5 48.5 7.0 6.6 55.0
3600 53.4 48.4 5.0 7.5 54.7
3500 53.8 47.3 6.5 7.5 55.2
3300 55.5 48.1 7.4 6.9 54.8
3000 54.4 47.7 6.7 6.7 54.7
2700 52.0 47.0 5.0 6.9 55.3
2500 51.3 45.8 5.5 6.9 54.8
2400 50.4 46.0 4.4 6.9 54.5
2100 51.3 45.6 5.7 6.7 54.5
2000 51.5 45.1 6.4 6.7 54.2
1800 49.7 44.6 5.1 6.6 55.4
1500 48.7 43.1 5.6 6.6 54.3
1200 49.1 42.5 6.6 6.6 54.1